- SECTION 07724
-
- ROOF HATCHES AND VENTS
- NOTE ** Naturalite hatches, heat and smoke vents; metal
- lids, plastic domes, drop out domes.
- NOTE **
- NOTE ** This section is based on products manufactured by
- Naturalite Skylight Systems, Butler Manufacturing
- Company, which is located at:
- NOTE ** 803 Airport Road
- NOTE ** P.O.Box 629
- NOTE ** Terrell, TX 75160
- NOTE ** Tel: (800) 259-7941
- NOTE ** Fax: (972) 551-6129
- NOTE **
- NOTE ** SECTION 07724 - ROOF HATCHES AND VENTS, Copyright
- 1997, The Architect's Catalog, Inc.
- NOTE ** HEAT AND SMOKE VENTS WITH PLASTIC DOMES:
- NOTE **
- NOTE ** CONDENSATION: Under certain conditions of high
- humidity and/or large inside to outside temperature
- differentials, condensation may occur on the
- aluminum framing and plastic glazing material.
- Double glazing will usually reduce the occurrence
- of condensation on the glazing, but will not
- totally eliminate it. Since plastic glazing cannot
- be hermetically sealed, condensation can form
- between the double layers of plastic but it will
- normally dissipate as the air space is heated by
- the sun. Sealed domes, where the flanges are
- sealed together ("bed" sealed), are more resistant
- to the formation of condensation and will reduce
- accumulation of dust and foreign matter. Sealed
- domes are available at additional cost.
- NOTE ** PLASTIC GLAZING: Acrylic plastic is the standard
- glazing type, in clear and 3 standard colors. A
- full range of custom translucent and transparent
- tints is also available. Polycarbonate sheet may
- be required for greater impact resistance or to
- meet some fire code requirements. Refer to your
- local building code for acceptable types and
- possible square foot area restrictions. Do not use
- abrasion resistant plastic materials for domes,
- since they should not be thermoformed.
-
- PART 1 GENERAL
-
- 1.1 SECTION INCLUDES
- NOTE ** Delete any products not required for this project.
-
- A. Roof hatches (scuttles).
-
- B. Heat and smoke vents, UL/FM labelled.
-
- C. Heat and smoke vents, non-labelled.
-
- D. Heat and smoke vents, drop-out dome type, FM labelled.
-
- 1.2 RELATED SECTIONS
- NOTE ** Delete any sections below not relevant to this
- project; add others as required.
-
- A. Section 07510 - Built-Up Bituminous Roofing.
-
- B. Section 07550 - Modified Bituminous Sheet Roofing.
-
- C. Section 07530 - Elastomeric Membrane Roofing.
-
- D. Section 07620 - Sheet Metal Flashing and Trim.
-
- E. Section 07610 - Sheet Metal Roofing.
-
- 1.3 REFERENCES
- NOTE ** Delete references from the list below that are not
- actually required by the text of the edited
- section.
-
- A. AAMA 1605.1 - Voluntary Standard Uniform Load Test
- Procedure for Plastic Glazed Skylights by Uniform Static
- Air Pressure Difference; American Architectural
- Manufacturers Association.
-
- 1.4 SUBMITTALS
-
- A. Submit under provisions of Section 01300.
-
- B. Product Data: Manufacturer's descriptive literature,
- specifications, use limitations and recommendations.
-
- C. Shop Drawings: Prepared specifically for this project,
- include:
- 1. Detailed plans and elevations, details of framing
- members, materials, sealants, fasteners, and anchors.
- 2. Type and thickness of formed flashing and closures.
- 3. Details of interface with adjacent materials.
- NOTE ** Delete the following paragraph if colors are
- completely specified or indicated on the drawings.
-
- D. Selection Samples: Two sets of color charts or samples,
- for selection of colors.
-
- E. Glazing Samples: Two pieces of plastic glazing material
- in specified color, for verification.
-
- 1.5 QUALITY ASSURANCE
-
- A. Manufacturer Qualifications: Minimum of 10 years
- experience in the fabrication and installation of similar
- products.
-
- B. Installer Qualifications: Minimum of 2 years experience
- in installation of similar units.
-
- 1.6 DELIVERY, STORAGE, AND HANDLING
-
- A. Arrange deliveries to avoid delays but to minimize on-
- site storage.
-
- B. Deliver products in labelled packages.
-
- C. Deliver, handle, and store in strict compliance with
- manufacturer's instructions and recommendations.
-
- 1.7 WARRANTY
-
- A. Provide written warranty signed by manufacturer that
- products are free of defects in materials and
- workmanship. Include repair or replacement of work which
- exhibits defects for five years from date of completion.
- Defects are defined as uncontrolled leakage of water and
- abnormal aging or deterioration.
-
- PART 2 PRODUCTS
-
- 2.1 MANUFACTURERS
-
- A. Provide products made by Naturalite Skylight Systems,
- Butler Manufacturing Company, P.O. Box 629, 750 Airport
- Road, Terrell, TX 75160. ASD. Tel: (800) 527-4018.
- Fax: (972) 551-6420.
- NOTE ** Delete one of the two following paragraphs;
- coordinate with Division 1 requirements. If other
- manufacturers must be listed, Plasteco and Wasco
- Products Inc. may manufacture products of
- equivalent performance.
-
- B. Requests for substitution will be considered in
- accordance with provisions of Section 01600.
-
- C. Substitutions: Not permitted.
-
- D. For manufacturers not listed, submit evidence of ability
- to provide products that meet both performance and
- product requirements, including list of projects of
- similar design and complexity completed within the last 5
- years.
-
- E. Provide primary materials that are made by a single
- manufacturer.
-
- 2.2 ROOF HATCHES AND VENTS
-
- A. Roof Hatches and Vents - Performance Requirements:
- Design to withstand the following loads:
- NOTE ** Enter the required performance values in the
- paragraphs below. Hatches and vents used in low-
- rise construction where the roof elevation is 60
- feet or less above grade should be designed to
- support a snow load of 20 psf and negative wind
- pressure of 20 psf, minimum. Greater capacity may
- be required depending on code requirements or
- project location. Heat and smoke vents are also
- specified to resist opening under up to 30 psf wind
- uplift.
- 1. Snow load: ___ psf (___ kPa).
- 2. Wind load: ___ psf (___ kPa) negative.
- 3. Seismic loads: As required by applicable code.
- 4. Dead loads.
- 5. Plastic Dome Lids: Show compliance with wind load
- requirements by testing in accordance with AAMA
- 1605.1.
-
- B. Roof Hatches: Factory-assembled units, complete with
- pintle hinges, compensating and hold open extension
- springs, bulb curb gasket, inside latch, and padlock
- hasp. Provide the following:
- 1. Insulated Metal Lid:
- a. Frame: 0.078 inch (2.0 mm) thick extruded
- aluminum.
- b. Cover: 0.090 inch (2.3 mm) thick aluminum.
- c. Cover: 18 gage (1.2 mm) galvalume.
- d. Insulation: 1 inch (25 mm) thick fiberglass.
- e. Liner: 0.040 inch (1.0 mm) thick aluminum.
- 2. Lid with Dome:
- a. Type: Single dome.
- b. Type: Double dome.
- c. Dome: Acrylic plastic glazing.
- d. Outer Dome Color: Colorless.
- e. Outer Dome Color: White.
- f. Outer Dome Color: Bronze.
- g. Outer Dome Color: Grey.
- NOTE ** Delete the following two paragraphs if single dome
- skylight has been specified. Otherwise, delete one
- of the two paragraphs.
- h. Inner Dome Color: Colorless.
- i. Inner Dome Color: White.
- NOTE ** Delete all but one of the following three
- paragraphs. The first is the standard curb; the
- second is a curb for use on metal roofs. The third
- is only for dome-type hatches for standing seam
- metal roofs.
- 3. Curb: 0.090 inch (2.3 mm) thick aluminum, with
- integral cap flashing, banded hardboard insulation
- and 3 inch (75 mm) mounting flange.
- 4. Curb: 18 gage (1.2 mm) galvalume inner wall panel,
- 24 gage (0.6 mm) galvalume outer wall panel,
- fiberglass insulation, and 0.040 inch (1.0 mm)
- aluminum liner.
- 5. Curb: 24 gage (0.6 mm) galvalume outer wall panel
- and vinyl-faced fiberglass insulation.
- 6. Curb Height: 9 inches (230 mm).
- 7. Curb Height: 12 inches (305 mm).
- 8. Curb Configuration: Standard.
- 9. Curb Configuration: For installation in cut-out in
- metal roof.
- 10. Curb Configuration: For installation in metal roof
- using custom seaming.
- 11. Curb Configuration: On low side match standing seam
- roof; mounting flange for inside fastening; cricket
- at upper side.
- 12. Frame Finish: Manufacturer's standard, mill finish.
- 13. Latch Handles: Exterior only.
- 14. Latch Handles: Interior only.
- 15. Latch Handles: Exterior and interior.
- 16. Size: As indicated on drawings.
- 17. Size: __________, inside curb dimension.
-
- C. Heat and Smoke Vents - Double Leaf: Automatically
- operated, mechanical type, factory-assembled.
- 1. UL listed.
- 2. FM listed.
- 3. UL and FM listed.
- NOTE ** Delete one of the following. The first is the
- standard curb. The second is for use on metal
- roofs and is FM approved only.
- 4. Curb: 0.125 inch (3 mm) aluminum walls, with
- integral cap flashing, self-flashing, with 4 inch
- (100 mm) wide mounting flange.
- 5. Curb: 14 gage (1.9 mm) galvalume inner wall panel
- and 24 gage (0.6 mm) galvalume outer wall panel, and
- fiberglass insulation; metal roof accessory kit
- furnished by manufacturer.
- NOTE ** Delete the following paragraph if not required.
- 6. Curb and Frame: Thermalized for condensation
- control.
- 7. Lids: Insulated, metal.
- 8. Lids: Plastic dome.
- a. Type: Single dome.
- b. Type: Double dome.
- NOTE ** Delete one of the following two paragraphs.
- Acrylic is FM approved; polycarbonate is required
- for UL approval.
- c. Domes: Acrylic plastic glazing.
- d. Domes: Polycarbonate plastic glazing.
- e. Outer Dome Color: Colorless.
- f. Outer Dome Color: White.
- g. Outer Dome Color: Bronze.
- h. Outer Dome Color: Grey.
- NOTE ** Delete the following two paragraphs if single dome
- skylight has been specified. Otherwise, delete one
- of the two paragraphs.
- i. Inner Dome Color: Colorless.
- j. Inner Dome Color: White.
- 9. Operation:
- a. Open lid automatically upon fusing of fusible
- link assembly.
- b. Open force sufficient to open despite 10 psf (4.8
- kPa) snow or wind load.
- c. Positively lock in the wide open position.
- d. Hold lid closed when subjected to up to 30 psf
- (14.4 kPa) wind uplift pressure.
- e. Automatically lock lid when manually closed.
- 10. Finish: Manufacturer's standard mill finish.
- 11. Hardware:
- a. Connect lid to curb with pintle hinges.
- b. Provide dampening devices to prevent failure of
- curb and frame due to stress produced by lid
- opening forces.
- c. Lid latch: Rotary slam type; allow lid to be
- manually opened from inside by a single release
- without disturbing the latch-fusible link
- assembly.
- NOTE ** Delete one of the following two paragraphs.
- Coordinate temperature required with fire alarm and
- suppression systems and local codes.
- d. Fusible link: 165 degree F (74 degree C) UL
- listed.
- e. Fusible link: 212 degree F (100 degree C) UL
- listed.
- NOTE ** Delete the following if not required. Inside
- release is mandatory.
- f. Additional outside manual release.
- g. Operating and latching mechanisms completely
- enclosed within unit and not exposed to weather.
- 12. Applicable approval labels attached to each unit.
- 13. Size: As indicated on drawings.
- 14. Size: __________, inside curb dimension.
-
- D. Heat and Smoke Vents - Single Leaf: Automatically
- operated, mechanical type, factory-assembled.
- 1. FM listed.
- 2. Curb: 0.125 inch (3 mm) aluminum back wall, 0.080
- inch (2.0 mm) aluminum side and front walls, with
- integral cap flashing, self-flashing, with 4 inch
- (100 mm) wide mounting flange.
- NOTE ** Delete the following paragraph if not required.
- 3. Curb and Frame: Thermalized for condensation
- control.
- 4. Lids: Insulated, metal, with 1 inch (25 mm) board
- insulation.
- 5. Lids: Plastic dome.
- a. Type: Double dome.
- b. Outer Dome: Polycarbonate plastic glazing.
- c. Inner Dome: Acrylic plastic glazing.
- d. Outer Dome Color: Colorless.
- e. Outer Dome Color: White.
- f. Outer Dome Color: Bronze.
- g. Outer Dome Color: Grey.
- h. Inner Dome Color: Colorless.
- i. Inner Dome Color: White.
- 6. Operation:
- a. Open lid automatically upon fusing of fusible
- link assembly.
- b. Open force sufficient to open despite 10 psf (4.8
- kPa) snow or wind load.
- c. Positively lock in the wide open position.
- d. Hold lid closed when subjected to up to 30 psf
- (14.4 kPa) wind up-lift pressure.
- e. Automatically lock lid when manually closed.
- 7. Finish: Manufacturer's standard mill finish.
- 8. Hardware:
- a. Connect lid to curb with pintle hinges.
- b. Lifting mechanism: Main springs, plus gas
- springs providing dampening to prevent failure of
- curb and frame due to stress produced by lid
- opening forces.
- c. Lid latch: Rotary slam type; allow lid to be
- manually opened from inside by a single release
- without disturbing the latch-fusible link
- assembly.
- d. Fusible link: 165 degree F (74 degree C) UL
- listed.
- e. Fusible link: 212 degree F (100 degree C) UL
- listed.
- NOTE ** Delete the following if not required. Inside
- release is mandatory.
- f. Additional outside manual release.
- g. Operating and latching mechanisms completely
- enclosed within unit and not exposed to weather.
- 9. Applicable approval labels attached to each unit.
- 10. Size: As indicated on drawings.
- 11. Size: __________, inside curb dimension.
- NOTE ** The following heat and smoke vents are not either
- UL or FM labelled.
-
- E. Heat and Smoke Vents: Automatically operated, mechanical
- type, factory-assembled.
- 1. Curb: 0.125 inch (3 mm) aluminum walls, with
- integral cap flashing, self-flashing, with 3 inch (75
- mm) wide mounting flange.
- 2. Curb: 18 gage (1.2 mm) galvalume inner wall panel
- and 24 gage (0.6 mm) galvalume outer wall panel, and
- fiberglass insulation; metal roof accessory kit
- furnished by manufacturer.
- 3. Curb Height: 9 inches (230 mm).
- 4. Curb Height: 12 inches (305 mm).
- 5. Lid Frame: 0.078 inch (2.0 mm) thick aluminum,
- secured directly to curb with pintle hinges.
- 6. Lids: Insulated, 0.080 inch (2.0 mm) thick aluminum,
- with 1 inch (25 mm) board insulation.
- 7. Lids: Plastic dome.
- a. Type: Single dome.
- b. Type: Double dome.
- c. Domes: Acrylic plastic glazing.
- d. Outer Dome Color: Colorless.
- e. Outer Dome Color: White.
- f. Outer Dome Color: Bronze.
- g. Outer Dome Color: Grey.
- h. Inner Dome Color: Colorless.
- i. Inner Dome Color: White.
- 8. Operation:
- a. Open lid automatically upon fusing of fusible
- link assembly.
- b. Open lid automatically when inside air pressure
- exceeds that required by local code.
- c. Positively lock in the wide open position.
- d. Automatically lock lid when manually closed.
- 9. Finish: Manufacturer's standard mill finish.
- 10. Fusible Link: 165 degree F (74 degree C) UL listed.
- 11. Fusible Link: 212 degree F (100 degree C) UL listed.
- NOTE ** Delete either of the two following paragraphs if
- not required.
- 12. Double lifting arms.
- 13. Additional outside manual release.
- 14. Size: As indicated on drawings.
- 15. Size: __________, inside curb dimension.
-
- F. Heat and Smoke Vents - Drop-Out Dome Type: Heat
- activated type, factory-assembled.
- 1. FM approved.
- 2. Frame: Extruded aluminum with integral condensation
- gutter.
- 3. Curb: Double aluminum wall construction with 3/4
- inch (19 mm) insulation and 3 inch (74 mm) wide roof
- flange.
- 4. Curb: 18 gage (1.2 mm) galvalume inner wall panel,
- 24 gage (0.6 mm) galvalume outer wall panel, and
- insulation; adaptable to standing seam roof without
- field welding, cricket on upper short side.
- 5. Curb: 18 gage (1.2 mm) galvalume outer wall panel
- and vinyl-faced fiberglass insulation; on low side
- match standing seam roof; mounting flange for inside
- fastening; cricket at upper side.
- 6. Double dome type, acrylic plastic.
- a. Outer Dome Color: Colorless.
- b. Inner Dome Color: Colorless.
- c. Inner Dome Color: White.
- 7. Operation: Heat activated inner dome drops out in
- less than five minutes at 500 degrees F (260 degrees
- C) when subjected to standard Factory Mutual fire
- exposure test.
- 8. Finish: Manufacturer's standard mill finish.
- 9. Applicable approval labels attached to each unit.
- 10. Size: As indicated on drawings.
- 11. Size: __________, inside curb dimension.
- NOTE ** Explosion Relief Vents are also available. Contact
- Naturalite with specific design criteria.
-
- G. Explosion Relief Vents:
-
-
- PART 3 EXECUTION
-
- 3.1 EXAMINATION
- NOTE ** DRAWING COORDINATION: The drawings should indicate
- the locations, types, and dimensions of the hatch
- and vent units, and show details of interface with
- adjacent construction.
-
- A. Take field measurements to verify that fabricated work
- will fit spaces intended.
-
- B. Verify that areas in which work is to be installed are
- ready for installation and that curbs are installed and
- level.
-
- C. Do not proceed until unsatisfactory conditions have been
- corrected.
-
- 3.2 INSTALLATION
-
- A. Install in strict accordance with manufacturer's
- instructions and recommendations and with approved shop
- drawings; provide a complete weatherproof assembly.
- NOTE ** The following paragraph coincides with the NRCA
- recommendation for roof-mounted units and curbs.
-
- B. Maintain dimension from top of curb to finish roofing of
- 8 inches (200 mm), minimum; provide additional blocking
- if required.
-
- C. Anchor securely to supporting structure, but allow for
- differential and thermal movement.
-
- D. Separate aluminum members from dissimilar metals with
- protective coating or sheet capable of preventing
- electrolytic action.
-
- E. Coordinate with other work.
-
- 3.3 CLEANING AND REPAIR
-
- A. Do not remove the "risk of fall" label from dome units.
-
- B. Remove labels, part number markings, sealant smears,
- handprints, and construction dirt; protect installed work
- from damage.
-
- C. Clean all exposed surfaces immediately prior to final
- inspection, using non-abrasive materials and methods
- recommended by manufacturer.
-
- D. Repair damaged components and finishes in accordance with
- manufacturer's recommendations; replace work that cannot
- be repaired to the satisfaction of the Architect.
-
- END OF SECTION
-